Next Article in Journal
Long-Term Homogeneity, Trend, and Change-Point Analysis of Rainfall in the Arid District of Ananthapuramu, Andhra Pradesh State, India
Previous Article in Journal
Application of Open Source Electronics for Measurements of Surface Water Properties in an Estuary: A Case Study of River Jadro, Croatia
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Evaluation of Legionella pneumophila Decrease in Hot Water Network of Four Hospital Buildings after Installation of Electron Time Flow Taps

Department of Translational Research and New Technologies in Medicine and Surgery, University of Pisa, 56126 Pisa PI, Italy
*
Author to whom correspondence should be addressed.
Water 2020, 12(1), 210; https://doi.org/10.3390/w12010210
Submission received: 26 November 2019 / Revised: 7 January 2020 / Accepted: 9 January 2020 / Published: 11 January 2020
(This article belongs to the Section Wastewater Treatment and Reuse)

Abstract

:
Legionella spp. control is a critical issue in hospital with old water networks. Chemical disinfection methods are applied as a control measure over prolonged time periods, but Legionella may be resistant to chemical agents in pipeworks with low flow and frequent water stagnation. We evaluated Legionella spp. colonization in the hot water network of Italian hospitals after the installation of time flow taps (TFTs). In the period between 2017 and 2019, TFTs were installed in four hospital water networks. They were programmed in order to obtain a hot water flow of 192 L/day from each TFTs. A continuous chlorination system (chlorine dioxide) and a cold water pre-filtration device were applied in all the buildings. Before and after TFT installation, Legionella spp. was investigated at scheduled times. Before TFT installation, Legionella pneumophila was detected in all the hospitals with counts ranging from 2 × 102 to 1.4 × 105 CFU/L. After TFT installation, a loss in Legionella pneumophila culturability was always achieved in the period between 24 h and 15 days. Total chlorine concentration (Cl2) was detected in the range between 0.23 and 0.36 mg/L while temperature values were from 44.8 to 53.2 °C. TFTs together with chemical disinfection represent a method which improve water quality and disinfectant efficacy, reducing Legionella colonization in dead-end sections.

1. Introduction

Legionella bacteria are environmental organisms found in water, soil, and other environments. Typically, they are transmitted to humans via the inhalation of contaminated aerosols and they may cause fulminant pneumonia or mild Pontiac fever. In particular, nosocomial Legionella spp. infection may affect immunosuppressed, transplant patients, and people undergoing aggressive chemotherapy [1,2].
According to the European Center for Disease Prevention and Control (ECDC), the rate of Legionnaires’ disease in Europe in 2017 was 18 cases per million inhabitants. During the same period, in Europe, 9 out of the 30 countries reported 28 legionellosis outbreaks, either community or hospital acquired. A 30% increase in the number of reported cases in Europe was observed in 2017 compared with 2016, with an increase in the overall European notification rate from 1.4 to 1.8 per 100,000 population [3,4].
The latest Italian data, related to 2017, give 2014 cases of Legionnaires’ disease in the Italian population, corresponding to a notification rate of 33.2 cases per million inhabitants. It must be noted that 2017 has seen an increase of 26% in the cases when compared with the previous three years. Of the 2014 notified cases, 124 (6.2%) were hospital acquired while 1580 (78.5%) were community-acquired infections [5].
International and Italian guidelines for Legionnaires’ disease control suggest that large hospital water networks and high-volume hot water storage tanks provide optimal conditions for Legionella colonization; the complexity of the water distribution systems and the presence of old and corroded pipelines and dead-end branches may promote the growth of Legionella in hospital water networks [6,7]. These critical points in water distribution systems cause a low water flow with a higher likelihood of biofilm development. Once microorganisms enter a system, they may be incorporated into biofilm, which is a primary cause of scarce water quality. Biofilm provides a nutrient source and protection from unfavorable environmental conditions. Several variables impact biofilm formation, including fluctuating water usage and transient stagnation [8,9,10,11]. In a previous study, we reported the experience of an Italian hospital where a cost-effectiveness strategy for Legionella control in the hot water distribution system was applied with continuous disinfection treatment and the installation of time flow taps (TFTs) in correspondence of all the dead-end branches, with the aim to increase the water flow of 196 L/day. Legionella pneumophila sg2–14 was initially detected in all the sampling points despite the presence of chemical disinfection. After eight months of TFTs activity, Legionella spp. was not detected anymore [12].
Based on that preliminary experience, the aim of this study is the application of the same method in teaching hospitals hosting high-risk patients. In this manuscript, we report the data related to the decrease in Legionella spp. contamination in the hot water networks of four hospitals located in Northwestern Tuscany (Italy) from 2017 to 2019.

2. Materials and Methods

2.1. Settings

The healthcare setting, called Hospital 1, is a 60-bed Internal and Emergency Medicine Hospital. This structure has been active since 1950. The hospital architectural structure is a monoblock with a central plate on four levels. Hospital 2 (Oncology Unit) is a monoblock with a central plate with three levels which has been active since 1972. It has 30 beds. Hospital 3 is a 320-bed General and Transplant Surgery Unit which has been active since 2007. It is organized in five blocks with four levels. Hospital 4 is a 11-bed Senology Unit which has been active since 1987. It has a central plate on four levels.

2.2. Water Disinfection

Within the Water Safety Plan (WSP) implementation program, hot water system treatment and a systematic monitoring program with sampling at points of use began in all hospitals.
The hospital WSP is a self-control manual aimed to manage the microbiological water risk from waterborne pathogens, such as Legionella spp. This protocol is a technical guide which describes the control critical points of the water systems (dead-end branches, pipework materials, devices, etc.), the water samplings for microbiological tests, the disinfection procedure of water networks, and all responsibilities related to plant management.
Municipal drinking water was pre-filtered before entering the hospital hot water distribution system. Despite the old and galvanized steel-made pipelines, the hot water network was treated with continuous chlorine dioxide disinfection.
Continuous disinfection with chlorine dioxide was applied in water networks. This method was used one day before TFT installation.
In hospital water stations, a chemical feed pump, chlorine solution tank, and chlorine residual monitoring kit were installed.
Hot water was recirculated in order to obtain an energy saving. After the identification of all the dead-end branches present in the hot water distribution system, TFTs were installed corresponding to the most critical points.
They present an adjustable flowmeter in order to measure the scheduled water flow. TFTs were programmed in order to obtain a hot water flushing of 1 minute every 2 h (192 liters per day from each TFT), as described elsewhere [12].
The TFTs, continuous chlorine dioxide disinfection, and municipal water pre-filtration plant were simultaneously installed in Hospital 1, Hospital 2, and Hospital 4. Four TFTs were placed in these buildings.
In Hospital 3, the continuous chlorination method was already present before TFT installation. Seven TFTs were simultaneously installed.

2.3. Hot Water Samplings and Legionella spp. Detection

According to all the hospital WSP programs, the hot water distribution system was sampled at the recirculation point of the central heating system (R), at the exit of the hot water production boiler (B), at each TFT, and at two points of use without TFTs (P1 and P2).
TFTs were installed close to some dead-end branches of the water networks (storage rooms, kitchens, and lockers rooms), while P1 and P2 were chosen from medical stays or surgery areas.
Legionella spp. detection and physical–chemical parameter assessment (total chlorine concentration, pH, and water temperature) were performed according to the following schedule:
  • One week before TFT installation (Time 0 or T0);
  • The day after TFT installation (Time 1 or T1);
  • Seven days after TFT installation (Time 2 or T2);
  • Fifteen days after TFT installation (Time 3 or T3);
  • One month after TFT installation, and then regularly on a monthly basis (Time 4 or T4, Time 5 or T5, etc.).
All physical–chemical parameter were measured in triplicate before and after TFT installation.
Samplings were performed after five minutes of water flushing. Hot water was collected in sterile bottles having sodium thiosulfate (20 mg/L). Temperature and total chlorine values were detected after the flushing.
Total chlorine concentration was determined by the colorimetric Visocolor HE® test (Macherey-Nagel, Düren, Germany).
Isolation of Legionella spp. in hot water samples was performed as suggested by the international standards procedure ISO11731 [13]. Briefly, one liter of water was filtrated through a 0.2 µm diameter membrane (Millipore, Billerica, MA, USA); the membrane was then immersed in 10 mL of the same water and sonicated for 5 min, allowing the detachment of the cells. The suspension was thermally inactivated by incubation at 50 °C for 30 min. Afterwards, 0.1 mL of the suspension was plated on Legionella BMPA selective medium (Oxoid Ltd., Basingstoke, Hampshire, UK) and the plates were placed in one incubator at 37 °C for 7–10 days within jars with a modified atmosphere (2.5% CO2) Finally, 10% of the Legionella-suspected colonies that grew on the medium were subjected to confirmation test using BCYE medium and BCYE without cysteine medium (Oxoid Ltd., Basingstoke, Hampshire, UK). Confirmed colonies were subjected to species and serogroup identification analysis using a multipurpose latex agglutination test (Legionella Latex Test, Oxoid Ltd., Basingstoke, Hampshire, UK).
Chemical samplings were taken at the same points chosen for microbiology tests. Chemical analyses were performed one week before TFT installation, six months after TFT installation, and then regularly on a six-monthly basis. Chemical parameters such as iron ions, zinc ions, and trihalomethanes (THMs) were determined as established by Council Directive 98/83/EC [14].

2.4. Statistical Analysis

The Kolmogorov–Smirnov test was performed to verify normality of distributions. For each hospital, Kruskal–Wallis test and Dunn′s test were used to compare Legionella spp. counts detected before and after TFT installations, as described elsewhere [12]. Power tests were carried out to estimate the sample sizes. The 1-beta values of the significant variables were >0.8, demonstrating that sample sizes were acceptable. The statistical analysis was fulfilled using IBM SPSS software package version 17.0.1.

3. Results

3.1. Legionella spp.

In Hospital 1, before the TFT installation, high Legionella pneumophila sg2–16 concentrations were detected in all the tested water point of use. Concentrations ranging from 2 × 102 to 2.6 × 104 CFU/L, with a mean value of 9.2 × 103 ± 1.1 × 103 CFU/L, were observed in the hot water samples. Following the implementation of TFTs and water treatment, from September 2017 onwards, we detected Legionella pneumophila sg2–16 for at least seven days, with concentrations ranging from 1 × 102 to 8.8 × 104 CFU/L and a mean count of 3.2 × 104 ± 2.9 × 104 CFU/L. A significant decrease in Legionella pneumophila sg2–16 contamination was obtained at the fifteenth and the thirtieth day (T3 and T4). After two months, Legionella spp. was no longer recovered (Figure 1).
High Legionella pneumophila sg1 concentrations were detected in Hospital 2 before TFT installation (from 3 × 102 to 1.5 × 103 CFU/L, mean of 8.8 × 102 ± 1.5 × 102 CFU/L). From April 2018, Legionella pneumophila sg1 was detected for at least four days, with a mean concentration of 1.8 × 102 CFU/L. Legionella spp. could not be detected after seven days (T2), (Figure 2).
In Hospital 3, despite the presence of the continuous chemical chlorination, Legionella pneumophila sg1 was detected in all the hot water samples at T0. Legionella concentrations ranged from 2.1 × 104 to 1.4 × 105 CFU/L (mean of 5.5 × 104 ± 3.1 × 103 CFU/L). After TFT installation, from November 2018, Legionella pneumophila sg1 was still present for at least two weeks (from 1 × 102 to 2.4 × 103 CFU/L). Absence of Legionella pneumophila sg1 was obtained from the fifteenth day (T3) (Figure 3).
Before the TFT installation, Legionella pneumophila sg1 was detected in Hospital 4. Legionella counts ranged from 1 × 102 to 1.9 × 104 CFU/L, with a mean value of 9.9 × 103 ± 2.8 × 103 CFU/L. Following the implementation of TFTs and water treatment, from February 2018, Legionella pneumophila sg1 was detected for one day (2.2 × 102 CFU/L). Legionella pneumophila sg1 was no longer detected from the seventh day (T2) (Figure 4).
In all hospitals, statistically significant reductions of Legionella counts were detected from the period were TFTs were absent to the period when the water flushing was increased (p < 0.001).

3.2. Physical–Chemical Parameters

In all hospitals, good chemical quality was observed in all hot water samples, and all values were within the limits recommended by Council Directive 98/83/EC [14].
In Hospital 1, the hot water temperature ranged from 36.4 ± 1.9 to 48.4 ± 2.8 °C before TFT installation. From the first day, mean temperature values ranged from 45.5 ± 3.2 and 53.2 ± 1.6 °C while continuous chlorination was maintained at mean values between 0.23 ± 0.04 to 0.31 ± 0.06 mg/L (Table 1).
Before TFT installation, the hot water temperature ranged from 35.8 ± 3.9 and 43.5 ± 8.4 °C in Hospital 2.
After TFT installation, the mean temperature values ranged from 46.6 ± 2.1 and 51.4 ± 1.7 °C, while the continuous chlorination was maintained at mean values between 0.23 ± 0.06 to 0.35 ± 0.04 mg/L (Table 2).
In Hospital 3, total chlorine concentrations were between 0 to 0.1 ± 0.02 mg/L, while hot water temperature values ranged from 32.8 ± 1.8 to 50.7 ± 1.6 °C before TFT installation. Continuous chlorination was maintained at mean values between 0.25 ± 0.01 to 0.40 ± 0.01 mg/L, while mean temperature values ranged from 44.8 ± 1.8 and 50.7 ± 1.6 °C (Table 3).
In Hospital 4 the water temperature values ranged from 32.4 ± 1.8 to 39.9 ± 3.2 °C at T0.
From the first day the mean temperature values ranged from 46.4 ± 2.2 to 50.1 ± 1.9 °C and the continuous chlorination was maintained at mean values between 0.28 ± 0.06 and 0.36 ± 0.04 mg/L (Table 4).

4. Discussion

According to literature, Legionella spp. control is needed in hospital settings, mostly in high-risk areas hosting immunosuppressed patients [15,16]. International and Italian guidelines [6,7] recommend the application of control measures to ensure good microbiological quality in hospital water networks. The choice of an adequate and continuous physical or chemical disinfection system may prevent the occurrence of waterborne pathogen colonization in hospital water plants [17], but the complete eradication of Legionella spp. seems mostly improbable if the colonization is high and the water network is old, large, and complex, with critical points [18]. In spite of the age of the water plant and the presence of continuous chlorination in Hospital 3, we detected the presence of high Legionella pneumophila concentration in hot water samples. This is due to the low hot water use in the hospital, which caused the persistence of Legionella spp. bacteria in biofilm, as described in our preliminary study [12]. In fact, the presence of dead-end branches in water networks allows the biofilm growth in points where the disinfectant cannot be effective against microorganisms [19].
Despite the different number of hospital levels or beds, the amount of dead-end branches detected in hot water networks were the same, with the exception of Hospital 3. In fact, we installed four TFTs in Hospital 1, Hospital 2, and Hospital 4, while seven TFTs were installed in Hospital 3.
The choice of TFT installation points depends on the kind of subjects (patients, healthcare workers, etc.) present in those areas. We avoided TFT installation in stays areas, surgeries, and medical offices in order to limit the exposition to contaminated aerosol during TFT installation.
These devices were mostly placed in storage rooms, kitchens, and locker rooms.
The TFT installation occurred in correspondence with dead-end sections in all the hospitals and the implementation of continuous chemical chlorination in Hospital 1, Hospital 2, and Hospital 4, and the municipal water pre-filtration devices allowed Legionella pneumophila decontamination during the period between T1 (24 h) and T4 (one month). As shown in Figure 5, Legionella pneumophila colonized all hospitals at T0 and T1. Contaminations persisted in Hospital 1 for one month and in Hospital 3 for seven days, despite the presence of total chlorine concentrations higher than 0.25 mg/L. After two months, Legionella pneumophila was no longer detected. Moreover, in all hospitals, the increase of temperature values was obtained from T0 to T1. This is due to the maintenance works on the hot water networks performed during TFT installation. Considering the low hot water temperatures detected at T0 (≤40 °C), we increased this value, in order to achieve boiler water temperatures of at least of 50 °C. According to recent studies, the increase in hot water temperature, lack of water stagnation, and application of good hydraulic practices play a role in Legionella spp. control in water networks [20,21,22].
Our results show that water flushing eases the chlorine dioxide efficacy in water networks. A reduction of stagnant water reduces biofilm growth, which is considered as a form of microorganism resistant against chemical disinfectants, such as chlorine dioxide, applied in water networks [23,24].
Literature data has shown the impact of unsteady flow on drinking water quality. Considering that stagnation promotes bacterial accumulation, special attention should be given to the biological quality of drinking water where consumption is variable. Interactions between hydraulics and biofilm structures are complex, and bacteria may be released from the biofilm into water after only 1 h of stagnation, allowing water quality degradation [22,23,24,25].
In conclusion, our study continues the assessment of TFT device applications from our previous work [12]. The aim of the TFTs was to increase the efficacy of the water disinfection system. In fact, TFT installation is considered a good cost-effective method which helps maintain disinfectant levels throughout the system [26]. Although the periods of contamination decrease were long, this method could represent a valid choice for improving drinking water quality and disinfectant efficacy, reducing the critical section of water plants and biofilm maturation in dead-end branches.

Author Contributions

A.B. and G.P. conceived and designed the experiments. M.T., B.C., P.V. and A.L.C. performed the experiments and wrote the paper. T.M., C.B. and E.D.V. performed the water samplings. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

All authors have no conflict of interest to declare.

References

  1. Oda, N.; Hirahara, T.; Fujioka, Y.; Mitani, R.; Takata, I. Legionella Pneumonia Following the Heavy Rain Event of July 2018 in Japan. Intern Med. 2019, 58, 2831–2834. [Google Scholar] [CrossRef] [PubMed]
  2. Muldrow, L.L.; Tyndall, R.L.; Fliermans, C.B. Application of flow cytometry to studies of pathogenic free-living amoebae. Appl. Environ. Microbiol. 1982, 44, 1258–1269. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  3. European Centre for Disease Prevention and Control. Legionnaires’ Disease. Annual Epidemiological Report for 2017; European Centre for Disease Prevention and Control Stockholm: Solna, Sweden, 2019; pp. 1–6. Available online: https://www.ecdc.europa.eu/en/publications-data/legionnaires-disease-annual-epidemiological-report-2017 (accessed on 12 November 2019).
  4. Alexandropoulou, I.G.; Ntougias, S.; Konstantinidis, T.G.; Parasidis, T.A.; Panopoulou, M.; Constantinidis, T.C. Environmental surveillance and molecular epidemiology of waterborne pathogen Legionella pneumophila in health-care facilities of Northeastern Greece: A 4-year survey. Environ. Sci. Pollut. Res. Int. 2015, 22, 7628–7640. [Google Scholar] [CrossRef] [PubMed]
  5. Superior Institute of Health. Rapporto Annuale Sulla Legionellosi in Italia Nel 2017; Superior Institute of Health: Rome, Italy, 2018; Volume 31, pp. 1–24. Available online: http://www.legionellaonline.it/notiziari_ISS.htm (accessed on 12 November 2019).
  6. World Health Organization. Legionella and the Prevention of Legionellosis; World Health Organization: Geneva, Switzerland, 2007; pp. 1–276. Available online: https://www.who.int/water_sanitation_health/publications/legionella/en/ (accessed on 12 November 2019).
  7. Superior Institute of Health. Linee guida per la prevenzione ed il controllo della legionellosi; Superior Institute of Health: Rome, Italy, 2015; pp. 1–149. Available online: http://www.salute.gov.it/portale/documentazione/p6_2_2_1.jsp?id=2362 (accessed on 12 November 2019).
  8. Whiley, H.; Hinds, J.; Xi, J.; Bentham, R. Real-Time Continuous Surveillance of Temperature and Flow Events Presents a Novel Monitoring Approach for Hospital and Healthcare Water Distribution Systems. Int. J. Environ. Res. Public Health 2019, 16, 1332. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  9. Rhoads, W.J.; Pruden, A.; Edwards, M.A. Interactive Effects of Corrosion, Copper, and Chloramines on Legionella and Mycobacteria in Hot Water Plumbing. Environ. Sci. Technol. 2017, 51, 7065–7075. [Google Scholar] [CrossRef] [PubMed]
  10. Flemming, H.C.; Wingender, J. The biofilm matrix. Nat. Rev. Microbiol. 2010, 8, 623–633. [Google Scholar] [CrossRef] [PubMed]
  11. Manuel, C.M.; Nunes, O.C.; Melo, L.F. Dynamics of drinking water biofilm in flow/non-flow conditions. Water Res. 2007, 41, 551–562. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  12. Totaro, M.; Valentini, P.; Costa, A.L.; Giorgi, S.; Casini, B.; Baggiani, A. Rate of Legionella pneumophila colonization in hospital hot water network after time flow taps installation. J. Hosp. Infect. 2018, 98, 60–63. [Google Scholar] [CrossRef] [PubMed]
  13. International Organization for Standardization. ISO 11731 Water quality—Enumeration of Legionella; International Organization for Standardization: Geneva, Switzerland, 2017; pp. 1–38. Available online: https://www.iso.org/standard/61782.html (accessed on 19 November 2019).
  14. The Council of the European Union. Council Directive 98/83/EC of 3 November 1998 on the Quality of Water Intended for Human Consumption; The Council of the European Union: Bruxelles, Belgium, 1998; pp. 1–23. Available online: https://op.europa.eu/en/publication-detail/-/publication/880a8575-7ee4-438e-b953-567df6719e26 (accessed on 19 November 2019).
  15. Montagna, M.T.; De Giglio, O.; Cristina, M.L.; Napoli, C.; Pacifico, C.; Agodi, A.; Baldovin, T.; Casini, B.; Coniglio, M.A.; D’Errico, M.M.; et al. Evaluation of Legionella Air Contamination in Healthcare Facilities by Different Sampling Methods: An Italian Multicenter Study. Int. J. Environ. Res. Public Health 2017, 14, 670. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  16. Kanamori, H.; Weber, D.J.; Rutala, W.A. Healthcare Outbreaks Associated with a Water Reservoir and Infection Prevention Strategies. Clin. Infect. Dis. 2016, 62, 1423–1435. [Google Scholar] [CrossRef] [PubMed]
  17. Totaro, M.; Casini, B.; Valentini, P.; Miccoli, M.; Giorgi, S.; Porretta, A.; Privitera, G.; Lopalco, P.L.; Baggiani, A. Evaluation and control of microbial and chemical contamination in dialysis water plants of Italian nephrology wards. J. Hosp. Infect. 2017, 97, 169–174. [Google Scholar] [CrossRef] [PubMed]
  18. Scaturro, M.; Dell’eva, I.; Helfer, F.; Ricci, M.L. Persistence of the same strain of Legionella pneumophila in the water system of an Italian hospital for 15 years. Infect. Control Hosp. Epidemiol. 2007, 28, 1089–1092. [Google Scholar] [CrossRef] [PubMed]
  19. Grayman, W.M. A quarter of a century of water quality modeling in distribution systems. In Eighth Annual Water Distribution Systems Analysis Symposium (WDSA); American Society of Civil Engineers: Cincinnati, OH, USA, 2012; Available online: https://ascelibrary.org/doi/abs/10.1061/40941%28247%294 (accessed on 19 November 2019).
  20. Gavaldà, L.; Garcia-Nuñez, M.; Quero, S.; Gutierrez-Milla, C.; Sabrià, M. Role of hot water temperature and water system use on Legionella control in a tertiary hospital: An 8-year longitudinal study. Water Res. 2019, 149, 460–466. [Google Scholar] [CrossRef] [PubMed]
  21. Bédard, E.; Laferrière, C.; Déziel, E.; Prévost, M. Impact of stagnation and sampling volume on water microbial quality monitoring in large buildings. PLoS ONE 2018, 13, e0199429. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  22. Fish, K.; Osborn, A.M.; Boxall, J.B. Biofilm structures (EPS and bacterial communities) in drinking water distribution systems are conditioned by hydraulics and influence discolouration. Sci. Total Environ. 2017, 593, 571–580. [Google Scholar] [CrossRef] [PubMed]
  23. Totaro, M.; Valentini, P.; Casini, B.; Miccoli, M.; Costa, A.L.; Baggiani, A. Experimental comparison of point-of-use filters for drinking water ultrafiltration. J. Hosp. Infect. 2017, 96, 172–176. [Google Scholar] [CrossRef] [PubMed]
  24. Szabo, J.; Minamyer, S. Decontamination of biological agents from drinking water infrastructure: A literature review and summary. Environ. Int. 2014, 72, 124–128. [Google Scholar] [CrossRef] [PubMed]
  25. Manuel, C.M.; Nunes, O.C.; Melo, L.F. Unsteady state flow and stagnation in distribution systems affect the biological stability of drinking water. Biofouling 2010, 26, 129–139. [Google Scholar] [CrossRef] [PubMed]
  26. Totaro, M.; De Vita, E.; Mariotti, T.; Bisordi, C.; Giorgi, S.; Gallo, A.; Costa, A.L.; Casini, B.; Valentini, P.; Privitera, G.; et al. Cost analysis for electron time-flow taps and point of use filters: A comparison of two methods for Legionnaires’ disease prevention in hospital water networks. J. Hosp. Infect. 2019, 103, 231–232. [Google Scholar] [CrossRef] [PubMed]
Figure 1. Legionella pneumophila sg2–16 counts at all the sampling points during the whole period of the study in Hospital 1. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
Figure 1. Legionella pneumophila sg2–16 counts at all the sampling points during the whole period of the study in Hospital 1. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
Water 12 00210 g001
Figure 2. Legionella pneumophila sg1 counts at all the sampling points during the whole period of the study in Hospital 2. (B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4).
Figure 2. Legionella pneumophila sg1 counts at all the sampling points during the whole period of the study in Hospital 2. (B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4).
Water 12 00210 g002
Figure 3. Legionella pneumophila sg1 counts at all the sampling points during the whole period of the study in Hospital 3. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4; TFT5 = time flow tap 5; TFT6 = time flow tap 6; TFT7 = time flow tap 7.
Figure 3. Legionella pneumophila sg1 counts at all the sampling points during the whole period of the study in Hospital 3. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4; TFT5 = time flow tap 5; TFT6 = time flow tap 6; TFT7 = time flow tap 7.
Water 12 00210 g003
Figure 4. Legionella pneumophila sg1 counts at all the sampling points during the whole period of the study in Hospital 4. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
Figure 4. Legionella pneumophila sg1 counts at all the sampling points during the whole period of the study in Hospital 4. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
Water 12 00210 g004
Figure 5. Legionella pneumophila counts (CFU/L) (A), total chlorine concentration (mg/L) (B), and temperature values (°C) (C) detected in all the hospitals.
Figure 5. Legionella pneumophila counts (CFU/L) (A), total chlorine concentration (mg/L) (B), and temperature values (°C) (C) detected in all the hospitals.
Water 12 00210 g005
Table 1. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 1. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
Table 1. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 1. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
BEFORE TFT INSTALLATION (September 2017)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B048.4 ± 2.86.52 ± 0.3152 ± 4.567 ± 2.6<3
R038.8 ± 1.96.50 ± 0.1269 ± 4.373 ± 1.9<3
P1038.8 ± 2.16.60 ± 0.1657 ± 3.982 ± 3.8<3
P2036.4 ± 1.96.57 ± 0.1198 ± 2.679 ± 6.2<3
TFT 1039.5 ± 1.66.58 ± 0.0974 ± 5.965 ± 7.1<3
TFT 2037.7 ± 1.76.70 ± 0.3161 ± 6.681 ± 6.0<3
TFT 3038.1 ± 2.56.60 ± 0.0969 ± 5.783 ± 5.7<3
TFT 4037.6 ± 2.26.52 ± 0.0670 ± 4.277 ± 6.4<3
AFTER TFT INSTALLATION (September 2017–July 2019)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B0.31 ± 0.0653.2 ± 1.66.59 ± 0.1859 ± 3.174 ± 3<3
R0.23 ± 0.0449.6 ± 2.16.60 ± 0.1177 ± 3.681 ± 4.1<3
P10.29 ± 0.0947.4 ± 1.26.56 ± 0.0963 ± 2.979 ± 3.3<3
P20.27 ± 0.0945.5 ± 3.26.5 ± 0.0877 ± 4.266 ± 4.2<3
TFT 10.26 ± 0.0848.6 ± 2.56.58 ± 0.1368 ± 3.878 ± 2.6<3
TFT 20.24 ± 0.0449.8 ± 1.56.51 ± 0.1071 ± 4.682 ± 5.2<3
TFT 30.26 ± 0.0548.3 ± 2.16.61 ± 0.0774 ± 2.384 ± 3.9<3
TFT 40.26 ± 0.0847.3 ± 2.26.58 ± 0.0975 ± 3.379 ± 3.6<3
Table 2. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 2. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
Table 2. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 2. B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4.
BEFORE TFT INSTALLATION (April 2018)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B043.5 ± 8.46.72 ± 0.1866 ± 2.264 ± 1.1<3
R037.6 ± 9.26.70 ± 0.1968 ± 2.166 ± 1.6<3
P1039.2 ± 5.46.74 ± 0.2161 ± 1.964 ± 1.0<3
P2035.8 ± 3.96.80 ± 0.2078 ± 1.180 ± 0.9<3
TFT 1038.8 ± 4.86.78 ± 0.1679 ± 1.885 ± 0.7<3
TFT 2039.4 ± 5.96.78 ± 0.1965 ± 2.087 ± 1.2<3
TFT 3039.1 ± 4.66.76 ± 0.1669 ± 2.286 ± 1.3<3
TFT 4036.9 ± 6.96.80 ± 0.2573 ± 2.179 ± 1.0<3
AFTER TFT INSTALLATION (April 2018–July 2019)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B0.35 ± 0.0751.4 ± 1.76.79 ± 0.1174 ± 0.1963 ± 0.19<3
R0.26 ± 0.0647.6 ± 1.96.70 ± 0.1069 ± 0.1568 ± 0.13<3
P10.24 ± 0.0947.6 ± 1.46.60 ± 0.1063 ± 0.1566 ± 0.14<3
P20.23 ± 0.0846.6 ± 2.16.62 ± 0.0975 ± 0.1181 ± 0.18<3
TFT 10.25 ± 0.0647.5 ± 2.16.68 ± 0.1179 ± 0.1784 ± 0.17<3
TFT 20.27 ± 0.0547.9 ± 1.66.61 ± 0.1470 ± 0.1282 ± 0.12<3
TFT 30.26 ± 0.0348.4 ± 1.76.64 ± 0.1174 ± 0.1785 ± 0.19<3
TFT 40.27 ± 0.0546.9 ± 1.86.78 ± 0.1176 ± 0.1881 ± 0.11<3
Table 3. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 3. (B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4; TFT5 = time flow tap 5; TFT6 = time flow tap 6; TFT7 = time flow tap 7).
Table 3. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 3. (B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4; TFT5 = time flow tap 5; TFT6 = time flow tap 6; TFT7 = time flow tap 7).
BEFORE TFT INSTALLATION (November 2018)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B0.10 ± 0.0240.6 ± 3.16.80 ± 0.2155 ± 0.854 ± 1.6<3
R0.05 ± 0.0135.8 ± 2.56.78 ± 0.2052 ± 0.961 ± 2.1<3
P10.1 ± 0.0540.1 ± 1.86.76 ± 0.1551 ± 1.153 ± 2.2<3
P20.0 ± 0.042.6 ± 1.66.78 ± 0.1760 ± 0.854 ± 2.5<3
TFT 10.05 ± 0.0141.1 ± 1.56.78 ± 0.1761 ± 0.961 ± 2.6<3
TFT 20.05 ± 0.0141.9 ± 2.26.75 ± 0.1556 ± 1.258 ± 3.6<3
TFT 30.05 ± 0.0142.6 ± 3.66.82 ± 0.2055 ± 1.957 ± 3.4<3
TFT 40.05 ± 0.0139.8 ± 3.26.82 ± 0.1956 ± 2.255 ± 5.0<3
TFT 50.05 ± 0.0239.5 ± 3.06.79 ± 0.1255 ± 2.660 ± 2.9<3
TFT 60.05 ± 0.0339.1 ± 2.96.80 ± 0.1654 ± 2.059 ± 2.3<3
TFT 70.05 ± 0.0132.8 ± 1.86.80 ± 0.0955 ± 1.856 ± 3.3<3
AFTER TFT INSTALLATION (November 2018–July 2019)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B0.40 ± 0.0150.7 ± 1.66.79 ± 0.1159 ± 0.1255 ± 0.12<3
R0.25 ± 0.1044.8 ± 1.86.70 ± 0.1059 ± 0.1657 ± 0.12<3
P10.31 ± 0.1046.5 ± 1.86.60 ± 0.1061 ± 0.1855 ± 0.11<3
P20.33 ± 0.1149.8 ± 2.26.62 ± 0.0965 ± 0.1363 ± 0.19<3
TFT 10.28 ± 0.1248.8 ± 2.06.68 ± 0.1161 ± 0.1162 ± 0.15<3
TFT 20.30 ± 0.0649.1 ± 1.86.61 ± 0.1462 ± 0.1068 ± 0.14<3
TFT 30.29 ± 0.0548.8 ± 1.66.64 ± 0.1163 ± 0.1174 ± 0.10<3
TFT 40.28 ± 0.0347.6 ± 1.66.78 ± 0.1166 ± 0.1361 ± 0.09<3
TFT 50.32 ± 0.0448.6 ± 1.26.80 ± 0.1061 ± 0.0969 ± 0.11<3
TFT 60.29 ± 0.0647.6 ± 1.46.69 ± 0.1059 ± 0.1364 ± 0.11<3
TFT 70.30 ± 0.0247.2 ± 1.36.72 ± 0.1159 ± 0.1266 ± 0.08<3
Table 4. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 4. (B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4).
Table 4. Mean values of physical–chemical and chemical parameters assessed at each sampling points before and after TFT installation in Hospital 4. (B = boiler; R = recirculation; P1 = point 1; P2 = point 2; TFT1 = time flow tap 1; TFT2 = time flow tap 2; TFT3 = time flow tap 3; TFT4 = time flow tap 4).
BEFORE TFT INSTALLATION (February 2019)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B039.9 ± 3.26.81 ± 0.1077 ± 0.5069 ± 0.18<3
R037.1 ± 2.56.78 ± 0.1281 ± 0.6068 ± 0.20<3
P1035.4 ± 2.96.76 ± 0.1376 ± 0.6264 ± 0.16<3
P2034.6 ± 2.66.80 ± 0.0974 ± 0.4178 ± 0.17<3
TFT 1033.2 ± 1.86.79 ± 0.1875 ± 0.5274 ± 0.24<3
TFT 2032.4 ± 4.26.78 ± 0.2071 ± 0.1979 ± 0.20<3
TFT 3033.3 ± 3.66.77 ± 0.1579 ± 0.2075 ± 0.19<3
TFT 4034.5 ± 2.76.74 ± 0.1181 ± 0.1676 ± 0.11<3
AFTER TFT INSTALLATION (February 2019–July 2019)
SAMPLING POINTTOTAL CHLORINE (Mean ± SD mg/L)TEMPERATURE (Mean ± SD °C)pH (Mean ± SD)IRON IONS (Mean ± SD µg/L)ZINC IONS (Mean ± SD µg/L)THMs (µg/L)
B0.36 ± 0.0450.1 ± 1.96.83 ± 0.0880 ± 0.1473 ± 0.17<3
R0.30 ± 0.0446.4 ± 2.26.79 ± 0.0883 ± 0.1271 ± 0.15<3
P10.34 ± 0.0748.5 ± 1.36.79 ± 0.0979 ± 0.0972 ± 0.18<3
P20.29 ± 0.0949.9 ± 2.06.78 ± 0.0976 ± 0.1080 ± 0.19<3
TFT 10.31 ± 0.0748.9 ± 2.16.81 ± 0.0679 ± 0.1580 ± 0.19<3
TFT 20.32 ± 0.0448.2 ± 1.96.70 ± 0.0876 ± 0.1479 ± 0.18<3
TFT 30.29 ± 0.0247.9 ± 2.36.72 ± 0.0983 ± 0.1978 ± 0.16<3
TFT 40.28 ± 0.0648.2 ± 2.26.79 ± 0.0876 ± 0.1877 ± 0.19<3

Share and Cite

MDPI and ACS Style

Totaro, M.; Mariotti, T.; Bisordi, C.; De Vita, E.; Valentini, P.; Costa, A.L.; Casini, B.; Privitera, G.; Baggiani, A. Evaluation of Legionella pneumophila Decrease in Hot Water Network of Four Hospital Buildings after Installation of Electron Time Flow Taps. Water 2020, 12, 210. https://doi.org/10.3390/w12010210

AMA Style

Totaro M, Mariotti T, Bisordi C, De Vita E, Valentini P, Costa AL, Casini B, Privitera G, Baggiani A. Evaluation of Legionella pneumophila Decrease in Hot Water Network of Four Hospital Buildings after Installation of Electron Time Flow Taps. Water. 2020; 12(1):210. https://doi.org/10.3390/w12010210

Chicago/Turabian Style

Totaro, Michele, Tommaso Mariotti, Costanza Bisordi, Erica De Vita, Paola Valentini, Anna Laura Costa, Beatrice Casini, Gaetano Privitera, and Angelo Baggiani. 2020. "Evaluation of Legionella pneumophila Decrease in Hot Water Network of Four Hospital Buildings after Installation of Electron Time Flow Taps" Water 12, no. 1: 210. https://doi.org/10.3390/w12010210

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop